Total Harmonic Distortion THDV dan THDI Per Fase Menggunakan ABB Power Meter M2M Mobus dan Fluke 435 pada Apartement Pondok Indah Residences

Authors

  • Deriel Apriliagung Universitas Pamulang
  • Juhana Universitas Pamulang
  • Sunardi Universitas Pamulang

Keywords:

Non-linear load, Harmonic Content, THDI, THDV, ABB Power Meter M2M Mobus, PQA Fluke 435

Abstract

The non-linear load on the power system has made the sinusoidal wave flowing in the system become very distorted which is expressed by the percentage of harmonic content, this study measured the harmonic content of current and voltage using ABB Power Meter M2M Mobus and PQA Fluke 435 measuring instruments. Furthemore, the measurent result are compared with the harmonic standards allowed based on the IEEE 519.1992 the maximum voltage distortion limit is 5% and the maximum current distortion limit is 20%. Measurement of THDI (%) and THDV (%) on each L₁, L₂, L₃. The result of this research show the state of maya tower harmonics by 2 tools namely ABB Power Meter M2M Mobus and PQA Fluke 435 starting at 10:00 – 16:00. Show the result that : 1. The shows the largest THDI and THDV on both tools are ABB Power Meter M2M Mobus THDI 18% and THDV 3%, PQA Fluke 435 THDI 19,3% and THDV 3,09%. 2. The difference in THDV measured by ABB Power Meter M2M Mobus and PQA Fluke 435 is around 0,09% while the difference in THDI measured by ABB Power Meter M2M Mobus and PQA Fluke 435 is around 1,3%. 3. THDV and THDI measured by both tools, namely ABB Power Meter M2M Mobus and PQA Fluke 435 at Pondok Indah Residences building right in the virtual LVMSB maya tower, are still included in the safe radar in the IEEE 519.1992 standard, namely THDV <5% and THDI <20%. With the condition of the electrical load at Pondok Indah Residences, it is recommended to review the LVMSB itself if necessary it would be better to install harmonic filter so that %THDI and %THDV are in a safe zone

References

Suprapto, Jaka. 2020. Analis Trafo Scott Mengatasi Penurunan Kapasitas Daya Akibat Distorsi Harmonik. Jakarta. Jurnal Ilmiah : Vol.12, No.2, ISSN 2655-5042.

Silalahi, Eva Magdalena., Widodo, Bambang., Purba, Robinson. 2021. Analisis Total Harmonic Distortion ( THD ) dan Arus Harmonik akibat Penggunaan Lampu Hemat Energi ( LHE ) dan Light-Emitting Diode ( LED ) secara Kolektif Pada Jaringan Tegangan Rendah. Sulawesi Tenggara. Jurnal Fokus Elektroda: Vol.06, No.1, ISSN 2502-5562.

Hidayat, Jhoni. 2022. Analisa Total Harmonisasi Distorsi ( THD ) Pada Beban Non Linier Jenis Laptop Idepad 110. Sumatera Utara. Jurnal Persegi Bulat: Vol.1, No.1, ISSN 2961-8193.

Ramli, Zoya Winona. 2021. Analisis dan Perancangan Mitigasi Harmonik Tegangan dan Arus di Poltekkes Kemenkes Semarang. Semarang. Jurnal Transient: Vol.10, No.2, e-ISSN: 2685-0206.

Rozak, Abdul Rozak., Rosiana, Elfirza. 2023. Analisis Pengukuran Power Quality Menggunakan Power Quality Analyzer Pada Perusahaan X. Banten. EPIC ( Journal Of Electrical Power, Instrumention and Control ): Vol.6, No.2, e-ISSN 2614-8595.

Juhana, J., & Rozak, O. A ( 2022 ). Reduksi Harmonik Pada Inverter Fasa Tiga Dengan Filter Pasif. EPIC Journal of Electrical Power Instrumention and Control.

Basir, Yuslan. 2021. Analisa Pengaruh Distorsi Harmonisasi Pada Air Conditioner Sistem Inverter. Palembang. Jurnal Desiminasi Teknologi: Vol.9, No. 1, ISSN 2503-5398.

Saurtika, I Made, 2020. Analisa Pengaruh Penggunaan Controller Pada Filter Aktif Shunt Terhadap Peredaman Distorsi Harmonisa. Denpasar Bali. Jurnal Spektrum: Vol. 7, No. 4, e-ISSN 2684-9186.

Additional Files

Published

22-10-2025

How to Cite

Deriel Apriliagung, Juhana, & Sunardi. (2025). Total Harmonic Distortion THDV dan THDI Per Fase Menggunakan ABB Power Meter M2M Mobus dan Fluke 435 pada Apartement Pondok Indah Residences. OKTAL : Jurnal Ilmu Komputer Dan Sains, 4(10), 672–680. Retrieved from https://journal.mediapublikasi.id/index.php/oktal/article/view/5701

Similar Articles

<< < 1 2 3 4 5 6 > >> 

You may also start an advanced similarity search for this article.

Most read articles by the same author(s)